[BUG] Wrong P_k value for the 1000 kVA LV transformer (factor of 10 too low) #658

Description

@joda9

Description

In edisgo/equipment/equipment-parameters_LV_transformers.csv the copper loss P_k
of the 1000 kVA standard transformer is clearly wrong — most likely a misplaced
decimal point. As a result the resistance of this transformer is modelled about a
factor of 10 too low in the network model.

Affected file

edisgo/equipment/equipment-parameters_LV_transformers.csv

name,S_nom,u_kr,P_k
#,MVA,%,MW
100 kVA,0.1,4,0.00175
160 kVA,0.16,4,0.00235
250 kVA,0.25,4,0.00325
400 kVA,0.4,4,0.0046
630 kVA,0.63,4,0.0065
800 kVA,0.8,6,0.0084
1000 kVA,1.0,6,0.00105   <-- 1.05 kW, should be ~10.5 kW (0.0105)

Why this is a bug

P_k (short-circuit / copper losses in MW) feeds into the per-unit resistance of the
transformer:

r_pu = P_k / S_nom — see edisgo/network/topology.py:213
(_load_equipment_data)

and from there into x_pu = sqrt((u_kr/100)^2 - r_pu^2).

Sanity check across the whole table:

Type P_k [kW] r_pu = P_k/S_nom
100 kVA 1.75 0.0175
160 kVA 2.35 0.0147
250 kVA 3.25 0.0130
400 kVA 4.6 0.0115
630 kVA 6.5 0.0103
800 kVA 8.4 0.0105
1000 kVA 1.05 0.00105

The P_k series increases monotonically (1.75 → 8.4 kW); the 1000 kVA value (1.05 kW)
even falls below the 100 kVA transformer and pulls r_pu down by a factor of 10.
This is not physically plausible.

Standard distribution transformers per EN 50464-1 have load losses of roughly
10.5 kW at 1000 kVA. The other rows of the table match those reference values
(e.g. 100 kVA = 1750 W, 630 kVA = 6500 W).

Expected behaviour

P_k for 1000 kVA should be 0.0105 MW (10.5 kW). This gives r_pu = 0.0105, which
lines up seamlessly with the 800 kVA value (0.0105).

Suggested fix

-1000 kVA,1.0,6,0.00105
+1000 kVA,1.0,6,0.0105

Impact

When a 1000 kVA distribution transformer is installed during grid reinforcement
(standard equipment / selection in reinforce_measures), its resistance is modelled
too low. Consequences:

  • The copper losses of this transformer are underestimated in the power flow.
  • The resistive voltage drop across the transformer is underestimated → potentially
    too optimistic voltage results and, in turn, possibly an understated reinforcement
    need whenever 1000 kVA transformers are involved.
  • x_pu changes only marginally (≈ 0.0600 → 0.0591) and stays real — so no crash,
    just silently wrong physics.

Activity

Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment

Metadata

Metadata

Assignees

Labels

bugcorrectnessSilently produces wrong numeric results (no crash) — high-value to fixgood first issueWell-scoped, low-risk — suitable for newcomers / student assistantspriority: high

Type

No type

Projects

No projects

    Milestone

    No milestone

    Relationships

    None yet

    Development

    No branches or pull requests

    Issue actions